5.7.3

Reaction times

The reaction time to an interrupted light array (ESPE) or a pressure-sensitive edge can be
determined by measuring the motor current reduction. To this end, the ESPE or pressure-
sensitive edge system can be activated (interrupted or triggered) during constant travel so that
the drive reverses.
The reaction times are independent of the sensor type (ESPE or pressure-sensitive edge). The
minimal response time amounts to 70 ms and the maximum response time amounts to 90 ms.
The delay caused by additional switchgear in the signal chain and by the sensor technology itself
must be added.
5.7.4

Stopping distances

The following table shows the expected stopping distances depending on the different
declaration ramps and different initial speeds, under consideration of a response time of 90 ms
(ESPE and / or pressure-sensitive edge, see section Reaction times (Page 171)).
Table 5-27
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA
Expected stopping distances [mm] under consideration of the ESPE execution time (90 ms)
Initial speed
[mm/s]
1400
300
350
400
450
500
550
600
650
700
750
5.7 Sensors and external sensor interface module
Set deceleration ramp [mm/s
1200
1000
59
65
72
75
83
93
93
103
116
113
125
142
134
149
170
158
176
201
183
204
234
209
235
270
238
267
308
268
302
349
Controllers
2
]
800
600
400
83
102
140
108
134
185
136
169
236
167
209
294
201
253
358
239
302
428
279
354
504
323
411
587
369
471
676
419
536
771
171