Test Run (As Of V1.12) - Siemens SIDOOR ATD4 W Series System Manual

Automatic door control units
Table of Contents

Advertisement

The two masks are stored in the following parameters:
Table 4-11
Parameter ID
p2080
p2081
Because DCMD is normally not to be considered bitwise (but as a numeric value), the mask for
DCMD should be either 0xFF or 0x00. As soon as the user enters a value unequal to 0 (0x01 to
0xFE), it is immediately and automatically corrected to 0xFF by the firmware.
Example:
To deactivate the NDG switchover via the fieldbus, the parameter value must be set to 0xFBFF
(see section (Page 319)).
4.3.12

Test run (as of V1.12)

Description of function
The test run is used to measure the closing and opening forces during final inspection and
commissioning. There is no reversing reaction during the test run.
The test run can be activated with the menu command "Test run" in the "General setup" menu
and via the fieldbus interface, parameter p95. The test run enables the reversing to be
deactivated after blocking for exactly the next door command. Afterwards, the test run function
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA
Masking of door commands
Value range
Default value:
0..65535
0xFFFF
(All bits of TSW1 from the
fieldbus are allowed to
pass.)
0..65535
0xFFFF
(All bits of the DCMD/ext.
DCMD are allowed to
pass.)
SIDOOR functions
4.3 Extended functions
Description
DCMD masking fieldbus
Each bit in the mask filters the corre‐
sponding bit in TSW1:
0: CMD bit is not allowed to pass
1: CMD bit is allowed to pass
DCMD masking FBLOCK
0: CMD bit is not allowed to pass
1: CMD bit is allowed to pass
109