Recommended Clearances; Mechanical Loading; Circuit Overloading; Reliable Earthing - Alcatel-Lucent OmniSwitch 6450 Series Hardware User's Manual

Table of Contents

Advertisement

Mounting OmniSwitch 6450 Series Switches

Recommended Clearances

Always allow adequate clearance at the front, rear, top, and sides of the switch. The following table shows
the recommended minimum clearances for adequate chassis cooling and access to cabling and
components at the front and rear of the chassis.
Location
OS6450
Top
0.875 inches (1/2 RU)
Bottom
No minimum clearance required. However, be sure that the bottom of the chassis is
not in direct contact with any equipment below.
Sides
2 inches
Rear
6 inches (see note below)
Front
6 inches (see note below)
Note. Clearance recommendations at the front and rear of chassis are for access to cabling and
components only and are not intended as a specific airflow requirement.

Mechanical Loading

Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to
uneven mechanical loading.

Circuit Overloading

Consideration should be given to the connection of the equipment to the supply circuit and the effect that
overloading of the circuit might have on overcurrent protection and supply wiring. Appropriate consider-
ation of equipment nameplate ratings should be used when addressing this concern.

Reliable Earthing

Reliable earthing of rack-mount equipment should be maintained. Particular attention should be given to
supply connections other than direct connections to the branch circuit (e.g. use of power strips).
OmniSwitch 6450 Series Hardware Users Guide
November 2011
General Installation Recommendations
page 3-3