Connection procedure, frames R3...R4
WARNING!
If the drive is connected on an IT (ungrounded) system, make sure you have
disconnected the EMC filter and Varistor (VAR). See
1. Remove the front cover as follows:
Loosen the retaining screw with a screwdriver (1a).
Push the front cover upward to uncouple top buckle (1b), and lift the cover
from the bottom outwards (1c).

Motor cable

2. Prepare the ends of the cable as illustrated in the figure. Two different motor
cable types are shown in the figures 2a and 2b.
Note: The bare shield will be grounded 360°.
2a
1c
2a
PE
Electrical installation 95
EMC filter (page
1b
85).