90 Electrical installation

Connecting the power cables

Connection diagram

1
For alternatives, see section
2
Use a separate grounding PE cable (2a) or a cable with a separate PE conductor (2b)
if the conductivity of the shield does not meet the requirements for the PE conductor
(see
Selecting the power cables (page
3
360° grounding is recommended if shielded cable is used. Ground the other end of the
input cable shield or PE conductor at the distribution board.
4
360° grounding is required.
5
External brake resistor (for frames R4...R8 only).
6
Use a separate grounding cable if the shield does not meet the requirements of IEC
61439-1 (see
Selecting the power cables (page
structed grounding conductor in the cable (see
Note: If there is a symmetrically constructed grounding conductor on the motor cable in
addition to the conductive shield, connect the grounding conductor to the grounding ter-
minal at the drive and motor ends.
Do not use an asymmetrically constructed motor cable for motors above 30 kW (see
the power cables (page
consumption, damages the motor bearing and even the motor.
Selecting the supply disconnecting device (page
68)).
68)). Earthing at the motor increases bearing current and power
68)) and there is no symmetrically con-
Motor cable shield (page
67).
71)).
Selecting