External Input Choke; Contents Of This Chapter; Why External Input Chokes Are Required; Specification - ABB ACS560 Hardware Manual

0.75 to 160 kw, 1.0 to 215 hp
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

External input choke

Contents of this chapter

This chapter describes about external input chokes available for the R0...R2 (2.6A
to 25A) frame sizes. In R0...R5 (33 A to 293 A) frame sizes, built-in DC swinging
choke is provided by default. DC swinging choke reduces 20% more harmonics in
partial loads due to its patented swinging choke technology and also helps in
protecting the drive from input variations and reduces DC ripple content.

Why external input chokes are required?

The external input choke protects against voltage spikes and reduces harmonics
in the line supply.

Specification

External input
CHK-01
choke name
Rated voltage
500
(V AC)
Frequency
50
(Hz)
Inductance
6.37
(mH)
Rated cur-
5
rent, IRMS (A)
Inductance
-5/+10
tolerance (%)
Cooling
Natural air
CHK-02
CHK-03
500
500
50
50
4.61
2.7
9
16
-5/+10
-5/+10
Natural air
Natural air
External input choke 233
14
CHK-04
CHK-05
500
500
50
50
1.475
1.13
25
40
-5/+10
-5/+10
Natural air
Natural air