Drive
U1. V1. W1 / U2. V2. W2 / R+. R- / DC+. DC- terminal
t y p e A C S 5 6 0
min. ( single
-
core and / mul-
ticore)
mm 2
3 phases U N = 400V (380...480V)
02A6-4
0.2/0.2
03A3-4
0.2/0.2
04A0-4
0.2/0.2
05A6-4
0.2/0.2
07A2-4
0.2/0.2
09A4-4
0.2/0.2
12A6-4
0.2/0.2
017A-4
0.5/0.5
025A-4
0.5/0.5
033A-4
0.5/0.5
039A-4
0.5/0.5
046A-4
0.5/0.5
062A-4
0.5/0.5
073A-4
0.5/0.5
088A-4
6
106A-4
6
145A-4
25
169A-4
95
206A-4
95
246A-4
2x50
293A-4
2x50

Terminal and lead-through data for the control cables

Control cable lead-throughs, wire sizes and tightening torques ( T ) are given below.
Max.( (single core
and/ multi-core )
mm 2
AWG
18
6/6
18
6/6
18
6/6
18
6/6
18
6/6
18
6/6
18
6/6
20
6/16
20
6/16
20
35/25
20
35/25
20
35/25
20
50/50
20
50/50
10
70
10
70
3
150
300 MCM
3/0
240
500 MCM
3/0
240
500 MCM
2x1/0
2x150
2x300MCM
2x3/0
2x150
2x300MCM
torque
AWG
N·m
8
0.5...0.6
8
0.5...0.6
8
0.5...0.6
8
0.5...0.6
8
0.5...0.6
8
0.5...0.6
8
0.5...0.6
4
1.2...1.5
4
1.2...1.5
2
2.5...4.5
2
2.5...4.5
2
2.5...4.5
1
4.0
1
5.6
2/0
5.6
2/0
5.6
30
30
30
40
40
Technical data 151
PE terminals
max
torque
mm 2
lbf·ft
N·m
0.4
6
1.2
0.4
6
1.2
0.4
6
1.2
0.4
6
1.2
0.4
6
1.2
0.4
6
1.2
0.4
6
1.2
1.0
6
1.2
1.0
6
1.2
3.3
10
1.5
3.3
10
1.5
3.3
16
1.5
3.0
16
1.5
4.1
16
1.5
4.1
25
2.2
4.1
35
2.2
22.1
50
9.8
22.1
70
9.8
22.1
70
9.8
29.5
2x35
9.8
29.5
2x50
9.8
F r a m e
size
R0
R0
R0
R0
R0
R0
R1
R2
R3
R3
R3
R3
R4
R4
R5
R5
R6
R7
R7
R8
R8

Hide quick links: