Front Option Slot 1 - ABB ACS560 Hardware Manual

0.75 to 160 kw, 1.0 to 215 hp
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Before you start the work, stop the drive and do the steps in section
safety precautions (page

Front option slot 1

By default, RIIO-01 module is provided in ACS560 standard R0...R2 drives. You can
remove the RIIO-01 module and can install BIO-01 and/or fieldbus adapter module
(+fxxx). If you are installing any of the fieldbus module, see section
cables
for suitable connector types.
For information on BIO-01 option, see
Note: BIO-01 module is applicable only for R0...R2 frame sizes.
To install RIIO-01, BIO-01 or/and fieldbus module, perform the following steps
1.
Remove the front cover(s). See section
R0...R2 (page
91).
If you have the BIO-01 option module, you can add a fieldbus option module
on top of it. For more information see
2. For RIIO-01, pull the plastic locking tab of the optional module that you want
to install.
132 Electrical installation
70 Electrical installation
3. Align the module with the option module slot in the front of the drive.
Installing option modules
4. Push the option module into position.
Note: In US deliveries, options are already installed at the factory.
Note: If you will install the FPBA
2. Pull the plastic locking tab of the option module up.
adapter module connectors
3. Carefully align the option module with the
4. Fully push the option module into
3
5. Push the plastic locking tab down until it
6. Tighten the locking screw.
Mechanical installation of option modules
See section
Overview of power and control connections
7. Connect the applicable control cables
slots for each module. Install the option modules as follows:
WARNING! Obey the instructions in chapter
you ignore them, injury or death, or damage to the equipment can occur.
Note: Slot 2 in frames R1...R5 is at U
supplies before installing or removing an I/O extension module.
Stop the drive and do the steps in section
16
before you start the work.
1. Remove the front cover(s) if not already removed. See page
105
(R5) or page
5. For RIIO-01, push the plastic locking tab down until it locks.
The figures for frames R1...R5 (page 133) and R6...R9 (page 135) show an example
of installing option modules.
18).
If you have the BIO-01 option module, you can add a fieldbus option module on
top of it.
01 module, see section
-
on page
77
for suitable connector types.
option module slot in the front of the drive.
position.
4
6
locks.
BIO-01
according to
Connecting the control
on page 62.
cables
potential. You must disconnect power
DC
Precautions before electrical work
63
(R6...R9).
Electrical installation 119
BIO-01 I/O extension module (page
Connection procedure: frames
BIO-01 I/O extension module (page
FPBA-01 PROFIBUS DP
page
34
for the available
Safety instructions
on page 13. If
on page
97
(R1...R4), page
Electrical
Routing the
213).
213).
3
4
5
6
RIIO-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents