140 Technical data
Drive
Nom-
Max.
Type
inal
cur-
ACS560
In
rent
I 1N
I max
A
017A-4
17
22.7
025A-4
25
30.6
033A-4
33
44.3
039A-4
39
56.9
046A-4
46
67.9
062A-4
62
76
073A-4
73
104
088A-4
88
122
106A-4
106
148
145A-4
145
178
169A-4
169
247
206A-4
206
287
246A-4
246
350
293A-4
293
418
1) Continuous current when its used in heavy duty applications, allows 130% of IHd for 1 minute every 10
minutes at 40 °C.
See definitions and notes in section

Definitions

U N
I 1
I max
I N
P N
I Ld
P Ld
Nominal use
I N
P N
A
A
kW
Hp
17
7.5
10
25
11
15
33
15
20
39
18.5
25
46
22
30
62
30
40
73
37
50
88
45
60
106
55
75
145
75
100
169
90
120
206
110
150
246
132
180
293
160
215
Nominal voltage
Nominal input current (rms) at 40 °C (104 °F)
Maximum output current. Available for two seconds at start.
Nominal output current. Maximum continuous rms output
current allowed (no overload).
Nominal power of the drive. Typical motor power (no overload-
ing). The kilowatt ratings apply to most IEC 4-pole motors. The
horsepower ratings apply to most NEMA 4-pole motors.
Maximum current with 110% overload, allowed for one minute
every ten minutes
Typical motor power in light-duty use (110% overload)
Output ratings
Light overload
use
I Ld
P Ld
(Con-
tinu-
ous)
A
kW
Hp
16.2
7.5
10
23.8
11
15
30.4
15
20
36.1
18.5
25
42.8
22
30
58
30
40
68.4
37
50
82.7
45
60
99.8
55
75
138
75
100
161
90
120
196
110
150
234
132
180
278
160
215
Definitions (page
Heavy-duty use
I Hd
P Hd
(Con-
tinu-
ous)
A
kW
Hp
12.6
5.5
7.5
17
7.5
10
24.6
11
15
31.6
15
20
37.7
18.5
25
44.6
22
30
61
30
40
72
37
50
87
45
60
105
55
75
145
75
100
169
90
120
206
110
150
1)
132
180
246
3AXD10000561047.xls A
140).
Frame
size
R2
R2
R3
R3
R3
R4
R4
R5
R5
R6
R7
R7
R8
R8

Hide quick links:

Advertisement

Table of Contents
loading