PTX10016 Router Quick Start Guide
Step 2–Unpacking the PTX10016
4
Figure 2: Airflow Through a PTX10016
Follow these guidelines:
For the cooling system to function properly, the airflow around the chassis must be
unrestricted.
If you are mounting a PTX10016 in a rack with other equipment, ensure that the exhaust
from other equipment does not blow into the intake vents of the chassis.
Leave at least 24 in. (61 cm) both in front of and behind the PTX10016 for service
personnel to remove and install hardware components. To be NEBS GR-63 compliant,
allow at least 30 in. (76.2 cm) in front of the rack and 24 in. (61 cm) behind the rack.
NOTE:
The chassis is maximally protected inside the shipping box. Do not
unpack it until you are ready to begin installation.
Ensure that you have the following parts and tools available to unpack the PTX10016:
A 13/32 in. (10 mm) open-end or socket wrench to remove the bracket bolts from the
shipping pallet
Copyright © 2018, Juniper Networks, Inc.