Signal evaluation
With the parameter assignment of the signal evaluation, you specify which edges of the
signals are counted.
You can select from the following options:
Signal evaluation
Single
Double
Quadruple
The parameter can be assigned with the following signal types:
● Incremental encoder (A, B phase-shifted)
● Incremental encoder (A, B, N)
Filter frequency
By configuring the filter frequency, you suppress interferences at the counting inputs A, B
and N.
The selected filter frequency is based on a pulse/break ratio of between around 40:60 and
around 60:40. This results in a specific minimum pulse/break time. Signal changes with a
duration shorter than the minimum pulse/break time are suppressed.
You can select from the following filter frequencies:
Filter frequency
100 Hz
200 Hz
500 Hz
1 kHz
2 kHz
5 kHz
10 kHz
20 kHz
50 kHz
100 kHz
200 kHz
TM Count 1x24V (6ES7138‑6AA01‑0BA0) technology module
Manual, 07/2019, A5E33002339-AD
Meaning
The edges of signal A are evaluated during a low level of signal B.
Each edge of signal A is evaluated.
Each edge of signals A and B is evaluated.
Minimum pulse/break time
4.0 ms
2.0 ms
800 µs
400 µs
200 µs
80 µs
40 µs
20 µs
8.0 µs
4.0 µs
2.0 µs
Configuring/address space
4.4 Fast Mode