Hardware interrupt: Compari-
son event for DQ0 occurred
Hardware interrupt: Compari-
son event for DQ1 occurred
Signal type
Invert direction
(counter inputs)
Signal evaluation
for counter inputs
Filter frequency
for counter inputs
Sensor type
Reaction to signal N
Frequency of
synchronization
Frequency of Capture func-
tion
High counting limit
Start value
Counting low limit
TM Count 1x24V (6ES7138‑6AA01‑0BA0) technology module
Manual, 07/2019, A5E33002339-AD
Parameter
1
1
1
1
1
1
1,4
1
1
1
4.3 Manual operation (without technology object)
Value range
Deactivated
Activated
Deactivated
Activated
Pulse (A)
Pulse (A) and direction (B)
Count up (A), count down (B)
Incremental encoder (A, B phase-shifted)
Incremental encoder (A, B, N)
Deactivated
Activated
Single
Double
Quadruple
100 Hz
200 Hz
500 Hz
1 kHz
2 kHz
5 kHz
10 kHz
20 kHz
50 kHz
100 kHz
200 kHz
Sourcing output
Sinking output
Push-pull (sinking and sourcing output)
No reaction to signal N
Synchronization at signal N
Capture at signal N
Once
Periodic
Once
Periodic
-2147483648...2147483647
-2147483648...0...2147483647
-2147483648...2147483647
Configuring/address space
Scope
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
43