Functions
4
Additional functions
4.6.8.1 Alarm management manager/subordinate
Note
66 | 180
The manager receives faults and alarms from its subordinates and displays the
higher priority alarm with the subordinate identification number in the order
received. If the manager has its own faults and alarms, it displays them instead.
The subordinate sends the fault or alarm with highest priority to the manager. If the
priority of a new fault or alarm is higher than that sent, the subordinate sends the
new one to replace the original.
The table below shows error codes and default alarm texts.
Priorities Fault
1
Condensation error
2
External fault input 1
3
External fault input 2
4
External fault input 3
5
External sensor error
6
External/remote sensor error
(physical)
7
External/remote sensor error
(physical)
8
External/remote sensor error
(physical)
9
External/remote sensor error
(physical)
1)
"x" indicates the subordinate identification number.
For other faults and alarms, see Fault and alarms function on KNX [➙ 125].
When P259 (subordinate identification) is set as 0, subordinate cannot send alarm
to manager.
Error code
Display on
Display on
subordinate
manager
COND
AL1
AL2
AL3
Er3
Er3
Er3
Er4
Er5
A6V11545892_en--_c
1)
CON.x
AL1.x
AL2.x
AL3.x
ER3.x
ER3.x
ER3.x
ER4.x
ER5.x