Obj
Object name
Room temp:
93
Temperature
Current cooling
setpoint (receive)
Communication object adjusts the current cooling setpoint
received by the thermostat from bus (see Setting and adjusting
setpoints [➙ 38]).
The range is 5...40 ° C.
S-Mode object needs to be enabled by setting Room temp:
Current setpoint to as group object in ETS.
Room operating
Comfort
94
mode: Status
Economy
(receive)
Protection
Actual room operating mode received by the thermostat
(Manager) from bus (considering time switch, user selection,
window contact, etc.) This state information is available via one 8-
bit enumeration.
ChangeOverWater
Heating: 1
95
status (send)
Cooling: 0
Sends the water changeover information.
ChangeOverWater
Heating: 1
96
status (receive)
Cooling: 0
Water changeover information received via bus.
97
Manual fan
0...100 %
command value
(send)
Sends the manual fan command value.
98
DC fan speed:
0...100 %
Maximum speed
heating
DC fan speed for maximum heating output received via bus.
A6V11545892_en--_c
Function
Type/
Flags
length
9.001
CWU
2 bytes
20.102
CWU
1 byte
1.100
CRT
1 bit
1.100
CWU
1 bit
5.001
CRT
1 byte
5.001
CWU
1 byte
Communication objects
Obj
Object name
DC fan speed:
99
0...100 %
Maximum speed
cooling
DC fan speed for maximum cooling output received via bus.
Built-in room air
100
Air quality
quality value
The value of the room air quality value (CO
sensor or external sensor is available on bus. (Manager)
External room air
101
Air quality
quality value
The thermostat (Subordinate) receives and works with the room
air quality value from an external sensor.
102
DC damper
0...100 %
demand
Indicates the control status of DC damper.
103
On/Off damper
On
demand
Off
Indicates the control status of On/Off damper.
Functions
Function
Type/
Flags
length
5.001
CWU
1 byte
9.008
CRT
2 bytes
) measured via built-in
2
9.008|
CWU
2 bytes
5.001
CRT
1 byte
1.001
CRT
1 bit
133 | 180