Siemens RDG20 KN Series Basic Documentation page 11

Room thermostats with knx communications
Hide thumbs Also See for RDG20 KN Series:
Table of Contents

Advertisement

Setting
Fan
Special functions
Inputs/outputs
A6V11545892_en--_c
Application selection via DIP switches or external commissioning software
(ACS, ETS and Siemens smartphone application PCT Go)
Parameter download with external commissioning software (ACS, ETS and
Siemens smartphone application PCT Go)
Reloading factory settings for commissioning and control parameters
1-speed, 3-speed or DC 0...10 V fan control on RDG20..KN and RDG26..KN
(automatic or manual fan)
Advanced fan control function, e.g. fan kick, fan start delay, selectable fan
operation (enable, disable, depending on heating/cooling mode, or min. and
max. speed setting)
Fan start depending on fan coil temperature (heating) to avoid cool air while
heating
Enabling fan output only in the 2
Switching fan speed from manual to automatic in the dead zone to avoid
energy waste (selectable function)
Swap function for 2-pipe and 2-stage application by switching the 1
nd
heating to 2
stage cooling
In 2-stage applications (2-/4-pipe), limit the number of heating or cooling
sequence to one
Control of 6-port ball valve for chilled and heated ceiling, DC 0...10 V,
DC 2...10 V and inverted signals DC 10...0 V, DC 10...2 V (RDG26..KN)
Control of 6-port ball valve as changeover (On/Off – open/close signal) and
PICV DC 0...10 V for
Chilled and heated ceiling/floor (RDG26..KN)
Fan coil application (RDG26..KN)
Control of 6-port ball valve via KNX S-Mode objects (RDG20..KN and
RDG26..KN)
Flow limitation function for PICV in heating mode (RDG26..KN)
Set holiday period to reduce energy consumption during absences (holidays)
2 multifunctional inputs X1, X2, and 1 multifunctional input/output U1 set as
input, selectable for:
Window contact switches operating mode to Protection
Presence detector switches operating mode to Comfort
Sensor for automatic heating/cooling changeover
Switch for manual heating/cooling changeover
External room temperature or return air temperature sensor
Dewpoint sensor
Enable electric heater
Fault input
Monitor input for temperature sensor or switch status
Supply air temperature sensor
Coil temperature sensor
External temperature limit
Hotel presence detector
1 multifunctional input/output U1 set automatically as output for:
4-pipe/2-stage as 2
IAQ control (damper and fan) (RDG204KN & RDG264KN)
Selectable relay functions
Switching off external equipment during Protection mode
Switching on external equipment (e.g. pump) during heating/cooling
demand
Output status heating/cooling sequence
Dehumidification/humidification control output
stage (2-pipe/2-stage, 4-pipe/2-stage)
nd
nd
stage cooling output (RDG26..KN)
Overview
2
Functions
st
stage
11 | 180