Siemens RDG20 KN Series Basic Documentation page 130

Room thermostats with knx communications
Hide thumbs Also See for RDG20 KN Series:
Table of Contents

Advertisement

Functions
4
Communication objects
Obj
Object name
35
Extended comfort
ON
mode status
OFF
Indicates the status of Comfort mode extension of manager.
36
External room
Temperature
temperature
value
The thermostat receives and works with the room temperature
from an external sensor.
37
Built-in room
Temperature
temperature
value
The value of the room temperature measured via built-in sensor or
external sensor is available on bus.
38
Frost alarm
No alarm
Alarm
Sends an alarm if the room temperature is below the frost alarm
setting.
39
Heat alarm
No alarm
Alarm
Sends an alarm if the room temperature is above the heat alarm
setting.
40
X1: Temperature
Temperature
42
X2: Temperature
44
U1: Temperature
Indicate the values of the temperature sensors connected to the
local inputs X1/X2/U1
41
X1: Digital
OFF
43
X2: Digital
ON
45
U1: Digital
Indicate the status of the digital inputs (adjusted by
P151/P154/P156) including considering of operating action
46
Heating/Cooling
Heating: 1
changeover
Cooling: 0
(receive)
Changeover information received via bus.
Default: Current mode before power down.
The same function is also available via local multifunctional input
X1/X2/U1 (P150, P153, P155).
Only one input source must be used, either local input X1/X2/U1or
KNX bus.
47
Heating/Cooling
Heating: 1
mode status
Cooling: 0
(send)
Sends the current heating or cooling mode of the thermostat.
130 | 180
Function
Type/
Flags
length
1.011
CRT
1 bit
9.001
CWU
2 bytes
9.001
CRT
2 bytes
1.005
CRT
1 bit
1.005
CRT
1 bit
9.001
CRT
2 bytes
1.001
CRT
1 bit
1.100
CWU
1 bit
1.100
CRT
1 bit
Obj
Object name
48
Application mode HVAC control
mode
0
Auto (default)
Heating and/or cooling
1
Heat
Heating only
2
Morning warmup*
Heating only
3
Cool
Cooling only
5
Precool*
Cooling only
6
OFF
Neither heating nor cooling
8
Emergency heat*
Heating only
9
Fan only
Fan runs at high speed
* Function handled like Heat (1) or Cool (3)
49
Dew point alarm
No alarm
Alarm
Indicates the status of dew point operation.
50
Enable fan
Enable
command value
Disable
Set fan mode to Auto (disable) or Manual (enable) by a KNX
control unit. If Manual, the value received on Fan command value
(52) will be used to command the fan speed.
Default: Enable
The last interaction wins – either from the local fan mode button or
via bus.
51
Fan operation
Auto
Manual
Indicates the status of the fan mode: Auto (0) or Manual (1).
52
Fan speed value
0...100 %
The fan can be set to a specified speed by a KNX control unit
when manual fan operation is enabled.
Speed
Fan command value
(physical KNX value)
1
1...33 %
2
34...67 % (86...170)
3
68...100 % (171...255)
Fan speed "0" is not supported by the thermostat and the fan
speed will remain unchanged.
Function
Type/
Flags
length
20.105
CWU
1 byte
1.005
CWU
1 bit
1.003
CWU
1 bit
1.001
CRT
1 bit
5.001
CWU
1 byte
(1...85)
A6V11545892_en--_c