Siemens RDG20 KN Series Basic Documentation page 144

Room thermostats with knx communications
Hide thumbs Also See for RDG20 KN Series:
Table of Contents

Advertisement

Functions
4
Control parameters
Diagnostics and test
Parameter Name
Diagnostics and test
d01
Application number
d02
X1 state
d03
X2 state
d04
U1 state
Test mode for checking the Y1/Y3 actuator's running
d05
1)
direction 5)
1)
Test mode for checking the Y2/Y4 actuator's running
d06
direction 5)
d08
Test mode for checking the Q1 output (ex P400
function)
d09
Test mode for checking the Q2 output (ex P401
function)
d10
Test mode for checking the Q3 output (ex P402
function)
d14
Firmware version
d15
Unit ID number (Serial number)
d16
Bootloader version
d17
Touch firmware version
d18
LCD version
Note: Parameter display depends on selected application and function.
1)
When output type is 3-position/3-wire, d05 and d06 are visible.
144 | 180
Range
0 = (No application)
1 = 2-pipe
2 = 2-pipe with electric heater
3 = 2-pipe with radiator
4 = 4-pipe
5 = 2-pipe / 2-stage
6 = 4-pipe with electric heater
7 = 4-pipe / 2-stage
8 = 4-pipe:6-port H/C (no fan)
9 = 4-pipe:6-port CO +PICV
"---" = Function not selected
0 = Not activated (for DI)
1 = Activated (DI)
0...49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100
= H/C Input open
"---" = Function not selected
0 = Not activated (for DI)
1 = Activated (DI)
0...49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100
= H/C Input open
"---" = Function not selected
0 = Not activated (for DI)
1 = Activated (DI)
2 = Activated (DC input)
3 = Activated (DC output)
0...49 °C = Current temp. value (for AI)
00
= H/C Input shorted
100
= H/C Input open
"---" = No signal on outputs Y1 and Y3
OPE = Output Y1 forced opening
CLO = Output Y3 forced closing
"---" = No signal on outputs Y2 and Y4
OPE = Output Y2 forced opening
CLO = Output Y4 forced closing
"---" = no signal at output Q1
OPE = output Q1 forced opening
CLO = output Q1 forced closing
"---" = no signal at output Q2
OPE = output Q2 forced opening
CLO = output Q2 forced closing
"---" = no signal at output Q3
OPE = output Q3 forced opening
CLO = output Q3 forced closing
v x-x-x is displayed
Unit ID is displayed (Serial number)
v x-x-x is displayed
v x-x-x is displayed
Dependencies
A6V11545892_en--_c