Note
Schedule overlap
Notes:
A6V11545892_en--_c
In Edit mode (value flashes), press
the change. The maximum number of set schedules is three per day.
In same schedule, the switching point for Economy cannot be earlier than that
for Comfort. E.g. Comfort is from 8:00 to 11:00 and Economy from 11:00 to
15:00. The edited switching point for Economy starts at 10:30. Afterwards,
press
once to confirm the change. No other schedule can be viewed until
the Economy switching point is set later than 11:00.
If the start time or end time of a new schedule lies within range of an existing
schedule, the schedule is combined with the existing one (OR function).
Example 1:
st
The 1
schedule is 8:00...12:00 and the 2
schedule starts at 10:00 and ends at 12:30, the schedule order is 1
nd
schedule (13:00 ...17:00) after the change is confirmed by
(8:00...12:30) and 2
pressing
.
Example 2:
st
The 1
schedule is 8:00...12:00 and the 2
schedule starts at 10:00 and ends at 13:30, the schedule is 8:00...17:00 after
the change is confirmed by pressing
For apartments with local scheduler and time / date synchronization via KNX
When the local scheduler is enabled (P005):
When P002 (operation via room op. selector) = 1 or 2, the manual selected
operating mode on the HMI remains in that mode until the user intervention to
select a new operating mode. P002 = 3 is no longer available.
When Auto is selected, the thermostat works according to the local scheduler
(operating mode switches between Comfort or Economy).
In Auto Comfort, changing the setpoint value does not switch the operating
mode to Comfort permanently.
In Auto Economy, changing the setpoint value switches the operating mode to
Auto Comfort with the new setpoint. Temporary timer symbol
Selecting green/red leaf function resets operating mode back to Auto Economy.
The local scheduler takes priority over the bus scheduler. KNX room "op.mode:
scheduler" has no impact on the operating mode.
Operating
P002 = 1
mode on LCD
AUTO
Switching operating mode between Comfort and Economy
ON
Operating mode remains permanent in Comfort
ECO
N/A
OFF
Operating mode remains permanent in Protection
Additional functions
to delete schedule or
nd
is 13:00 ...17:00. If the newly added
nd
is 13:00 ...17:00. If the newly added
.
P002 = 2
Operating mode remains permanent in Economy
Functions
4
(Esc) to cancel
st
schedule
is displayed.
P002 = 3