Comfort basic setpoint
Comfort setpoint
Economy heating setpoint
4)
Economy cooling setpoint
4)
A6V11545892_en--_c
The source can be one of the followings:
●
Local HMI
●
KNX tool
●
Central control unit
●
Siemens smartphone application PCT Go
The thermostat saves the setpoints to:
●
EEPROM in the form of parameters
●
Runtime memory
The figure below shows the interrelation:
1)
Only required for heating and cooling applications (see Setpoints and sequences
[➙ 98])
2)
LTE-Mode: Shift is added to the local shift
3)
S-Mode: The last option selected is always used, either S-Mode input or local
operation
4)
To display the S-Mode objects of the Economy heating and cooling setpoint
(P019/P020), set the control parameter "Room temperature: Economy setpoints" to
as group object in ETS tool
5)
Other functions:
●
If current humidity setpoint is not suitable for room humidity, setpoint shift is
activated via humidity control strategy (P451).
In cooling mode, a large difference between outside and indoor temperatures can
create discomfort and waste energy. The thermostat can track the outside
temperature via the bus and adjust the cooling setpoint to make sure the difference
Functions
Room temperature setpoints
4
39 | 180