• Check that the condensate produced during
operation fills the syphon and is regularly
drained in the draining pipe.
• Switch off the boiler by pressing the 12 (Fig.
7.15) key for 5 seconds until the
symbol appears on the LCD display (Fig.
7.14).
• Press the 12 key for 5 seconds until both
and
symbols appear on the dis-
play Fig. 7.15.
The LCD display displays the boiler tem-
perature (primary circuit) and the
symbols Fig. 7.16.
The boiler will now go through an ignition se-
quence and the burner will light.
If after four ignition attempts (about four min-
utes) the boiler does not function and a code
that alternates between the letter "E" and the
writing RESET appear on the LCD display, it
indicates that the safety lock-out has stopped
the boiler. The display background flashes
(Fig. 7.17).
Fig. 7.17
Press the reset key on the boiler control panel
12 (Fig. 7.15) to reset its functioning.
For the first lighting up and following mainte-
nance procedures for the gas supply, it may
be necessary to repeat the resetting operation
several times so as to remove the air present
in the pipework.
After five consecutive resetting attempts the
reset button is inhibited. To restore its func-
COMMISSIONING
tion it is necessary to switch the boiler off and
on from the electrical mains, using the fused
spur isolation switch fitted adjacent to the ap-
pliance.
7.9
With the burner on high flame close the gas
cock.
After four ignition attempts (about four min-
utes) the boiler does not function and a code
that alternates between the letter "E" and the
writing RESET appear on the LCD display, it
indicates that the safety lock-out has stopped
and
the boiler. The display background flashes
(Fig. 7.18).
Fig. 7.18
Press the reset key 12 on the boiler control
panel to reset its functioning.

7.10 Checking the flue system

The flue system should be visually checked
for soundness. Check all clamps, gaskets and
fixing are secure and tight.
Ensure that the flue terminal is sited correctly
in accordance with the flue fitting instructions
and Fig. 5.1 on page 30 of this manual.
To carry out a combustion check refer to the
instructions given in the section "Combustion
analysis check" on page 70 of this manual.
Reference figures are given in section "Techni-
cal data RINNOVA ADAPTIVE 30S (M300V.30
SR)" on page 26 (Flue gas figures).

Checking the ignition device