Condensate Pipe And Traps; Checking The Gas Supply Pressure; Checking The Inlet Pressure - Biasi RINNOVA ADAPTIVE 30S User Manual And Installation Instructions

Wall hung, fanflue, roomsealed, high efficiency gas boiler
Hide thumbs Also See for RINNOVA ADAPTIVE 30S:
Table of Contents

Advertisement

• switch off the electric power supply;
• press the 11 and 13 keys simultaneously
for 5 seconds (Fig. 7.4) (return to previous
level).
• Switch off the boiler by pressing the 12 (Fig.
7.4) key for 5 seconds until the
symbol appears on the LCD display (Fig.
7.3).
7.5

Condensate pipe and traps

The full length of the condensate pipe should
be check for leaks.
Before running the boiler, ensure that the built
in condensate trap and any other trap in the
drain system is correctly filled with water.
Fill the built in condensate trap by
removing the flue elbow and pour-
ing a cupful of water into the flue
outlet (Fig. 7.11).
Warning do not allow water to en-
ter the outer air intake
Fig. 7.11
An alternative, to the removal of the flue el-
bow, pour the water through the flue sampling
point (Fig. 7.12).
Fig. 7.12
COMMISSIONING
Sampling points
Flue exhaust
7.6
Checking the gas supply pres-
sure
This boiler has been factory tested to the
highest quality control standards and set
for the minimum and maximum gas work-
ing pressures, connected to a 1 m flue and
a gas supply pressure of 20 mbar.
Any variation in gas supply pressure or
flue length may result in the customer ex-
periencing a harmonic noise from the boil-
er. In these circumstances, it may be nec-
essary to reset the burner gas pressures
in accordance with section 11 Gas Valve of
the Service Manual.
It should be noted that a Flue Gas Analyser
is required for this procedure.
7.7

Checking the inlet pressure

• Remove the boiler front panel, see section
"Dismantling the external panels" on page
66.
• With the boiler switched on at full rate (maxi-
mum output power), check the supply pres-
sure by using the 25 point in Fig. 7.13 and
compare the value with that reported on
the Gas supply pressure table (minimum
inlet pressure) in section "Technical data
RINNOVA ADAPTIVE 30S (M300V.30 SR)"
on page 26.
• Ensure the test nipple 25 in Fig. 7.13 is firm-
ly closed.
- 49 -