Fitting the flue system

For a correct installation of the flue pipe, re-
fer to the sheet provided together with the
pre-selected kit.
The horizontal run of the flue pipes must in-
cline about 1.5 degrees (25 mm per meter);
therefore the terminal must be higher than
the intake at the boiler.
The standard horizontal flue kit must be fit-
ted horizontal as the inner flue exhaust pipe
is already angled with the correct incline.
CORRECT system for installing the wall
flue
A+S
ASA
Fig. 6.5
A = air intake
S = flue exhaust
- 38 -
INSTALLATION
6.8
The flue exhaust/air intake can be installed
in the mode:
C
C
13
The following kits to be connected to the
boiler are available:
Wall flue exhaust kit (Fig. 6.6 A)
This kit allows the flues to be exhausted in
the rear wall or at the side of the boiler.
Coaxial pipe Ø 60/100 (A)
Nominal length
Minimum length
Maximum length
Type C
Fig. 6.6
Vertical flue exhaust kit with 90° bend
(Fig. 6.6 B)
This kit allows the boiler exhaust axis to be
lifted by 635 mm.
The terminal must always exhaust horizon-
tally.

Choice of flue

C
C
33
53
63
The terminal must be higher
than the boiler.
13
B
A
0.915 m
0.5 m
10 m
90°
C
45°