5.7
Operating Instructions Web512 V2.6.x for Web-server II 1598

Web Link

If e.g. a fire alarm is presented (see page 13), it is possible to click a
hyperlink Info or Camera to get more information about the alarm
point and/or to connect to a web camera. The alarm points and links
are added / deleted in the Web Link tab.
Click New Link to add a row to the list.
Click Remove Link to remove a selected row from the list.
If many alarm points shall have the same link or if only the file name
in a path is different for the different alarm point, the Prefix 1 can be
used for Web Link 1 and Prefix 2 for Web Link 2.
Prefix 1: Type the prefix text in the cell.
Prefix 2: Type the prefix text in the cell.
Zone Address: Type the Zone Address for the alarm point (in the
cell).
Web Link 1 (Info): Type a link (a path) to a document (e.g. a
drawing) for more information regarding the alarm point.
NOTE! If for example the Prefix 1 checkbox is marked, the Prefix 1
text will be automatically added before the Web Link 1 text when the
site is downloaded to the Web-server II but the Prefix 1 text will never
be displayed in the Web Link 1 cell.
Web Link 2 (Camera): Type a link (a path) to a web-camera (or a
second document).
Example:
Prefix 1: http://panasonic-fire-security/
Web Link 1: Document_1.pdf
Will be downloaded to the Web-server II as follows:
http://panasonic-fire-security/Document_1.pdf
Prefix 1 