Operating Instructions Web512 V2.6.x for Web-server II 1598
The communication direction for a specified BS4 Loop (0-3) on a
specified expansion board 1584, Autronica interface Board (0-3), in a
specified Control Unit (00-29) can be locked.
Click A Dir. to lock the communication in the A-direction.
Click B Dir. to lock the communication in the B-direction.
Click Both to lock the communication in both directions at the same
time.
Calibrate outputs
Like menu H5/A1.
Click Request to start the calibration of supervised outputs in all
(99) control units or in a specified control unit (00-29).
Close Fire door
Click Request to collectively close all fire doors, i.e. programmable
outputs with a control expression containing one or more trigger
conditions Fire Door Closing (zone – address), in all (99) control
units or in a specified control unit (00-29).
Service – Act. Outputs
Click Act. Outputs to open the Service – Act. Outputs view:
NOTE! A latched interlocking output has to be reset via menu
H9/C3, i.e. Reset will not reset a latched interlocking output.
Loop unit Output
A specified Output (0-3) on a specified COM loop unit (Tech. No.)
can be activated.
Click Set to activate the output.
Click Reset to de-activate the output.
Voltage Output
A specified voltage Output (S0-S3) in a specified Control Unit (00-
29) can be activated.
Click Set to activate the output.
Click Reset to de-activate the output.