8.2.7 Compressor
WARNING: CONTAINS REFRIGERANT
 Evacuate the system and confirm that there is no refrigerant
left in the system before removing the four-way valve and
the compressor. (For R32 & R290, you should evacuate
the system with the vacuum pump; flush the system with
nitrogen; then repeat the two steps before heating up the
brazed parts. The operations above should be implemented
by HVAC professionals.
Remove the panel plate, connection of compressor on PCB (refer to
9.4.1 Panel plate and 9.4.2 Electrical parts) before disassembling
sound blanket.
1. Remove the fl ange nut of terminal cover and remove the terminal cover.
Terminal
Cover
Figure 134
8 6 |
Bosch Wall Mounted Ductless Split Air Conditioner / Heat Pump IDU-ODU - BTC 769102301 A (11.2022)
2. Disconnect the connectors.
Figure 135