7.6.15 Main Parts Check
Temperature sensor check
WARNING: ELECTRICAL HAZARD
 Be sure to turn off all power supplies or disconnect all wires
to avoid electric shock.
WARNING: PERSONAL INJURY
 Operate after compressor and coil have returned to normal
temperature in case of injury.
1. Disconnect the temperature sensor from PCB.
2. Measure the resistance value of the sensor using a multi-meter.
3. Check corresponding temperature sensor resistance value table.
Figure 62
The picture and the value are only for reference, actual condition and
specifi c value may vary.
6 2 |
Bosch Wall Mounted Ductless Split Air Conditioner / Heat Pump IDU-ODU - BTC 769102301 A (11.2022)