For some models:
If any one of the following conditions is satisfied, the unit enters
defrosting mode
If T3 or T4 is lower than -3°C for 30
seconds,Ts-T1 is lower than 5°C and compressor
running time is more than EE_TIME_DEFROST7.
If T3 or T4 is lower than -3°C for 30 seconds and
compressor running time is more than EE_TIME_
DEFROST7+30.
If any one of the following conditions is satisfied, defrosting ends and
the machine switches to normal heating mode:
T3 rises above TCDE1+4°C. (TCDE1=12C).
T3 maintained above TCDE2+4°C for 80
seconds. (TCDE2=2C)
Unit runs for 15 minutes consecutively in
defrosting mode.
6.4.5.1 Evaporator coil temperature protection
Figure 20
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level per 20 seconds.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
Bosch Wall Mounted Ductless Split Air Conditioner / Heat Pump IDU-ODU - BTC 769102301 A (11.2022)
6.4.6 Auto-mode
This mode can be chosen with the remote controller and the setting temperature
can be changed between 61°F~86°F (16°C~30°C)
In auto mode, the machine will choose cooling, heating or fan-only mode according
to T1,Ts, T4 and relative humidity.
Figure 21
If the setting temperature is modifi ed, the machine selects a new running function.
6.4.7 Dry mode
In dry mode, AC operates the same as auto fan in cooling mode.
All protections are activated and operate the same as they do that in
cooling mode.
Low Room Temperature Protection
If the room temperature is lower than 10°C, the compressor ceases operations and
does not resume until room temperature exceeds 12°C.
6.4.8 Forced operation function
Forced cooling mode: The compressor and outdoor fan continue to
run(fi xed at rated frequency), and the indoor fan runs at rated speed.
After running for 30 minutes, the AC will switch to auto mode with a
preset temperature of 24°C.
Forced auto mode: Forced auto mode operates the same as normal
auto mode with a preset temperature of 24°C.
When AC receives signals, such as switch on, switch off , timer on, timer
off , mode setting, temperature setting, fan speed setting, sleeping mode
setting, follow me setting, it will quit the forced operation.
Forced defrosting mode: Press AUTO/COOL button continuously for
5s under forced cooling mode to enter this mode. Indoor fan will stop,
defrosting lamp will light on. Quit this mode and turn off the unit when:
either quit normal defrosting, turn off by RC or Press AUTO/COOL
button continuously for 5s again.