Technical specifications
Technical specifications of IM 155-6 PN R1
The following table shows the technical specifications as of 11/2022. You can find a data
sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7155-6AU00-0HM0/td?dl=en).
Article number
General information
Firmware version
•
FW update possible
Product function
•
I&M data
•
Module swapping during operation (hot swapping)
•
Isochronous mode
Engineering with
•
STEP 7 TIA Portal configurable/integrated from version
•
PROFINET from GSD version/GSD revision
Configuration control
via dataset
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Short-circuit protection
Mains buffering
•
Mains/voltage failure stored energy time
Input current
Current consumption, max.
Inrush current, max.
I²t
Power loss
Power loss, typ.
Address area
Address space per module
•
Address space per module, max.
Address space per station
•
Address space per station, max.
Interface Module IM 155-6 PN R1 (6ES7155-6AU00-0HM0)
Equipment Manual, 11/2022, A5E51160307-AA
6ES7155-6AU00-0HM0
V6.0
Yes
Yes; I&M0 to I&M3
Yes; Multi-hot swapping
No
V18
GSDML V2.4.x
No
24 V
19.2 V
28.8 V
Yes
Yes
10 ms
700 mA
5 A
0.36 A²·s
2.4 W
288 byte
1 440 byte
7
47