Siemens SIMATIC ET 200SP Manual page 16

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Information on the BusAdapters is available in the BusAdapter
(https://support.industry.siemens.com/cs/ww/en/view/109751716) manual.
• BaseUnits
– BaseUnit BU type M0 for two IM 155-6 PN R1 incl. server module and two 24 V DC
Information on the BaseUnits is available in the BaseUnits
(https://support.industry.siemens.com/cs/ww/en/view/59753521) equipment manual.
• Labeling strips
• Reference identification label
You can find more information on the accessories in the ET 200SP Distributed I/O System
(https://support.industry.siemens.com/cs/ww/en/view/58649293) system manual.
Configuration limits for IO devices
Maximum number of connections to IO controllers
A connection to a redundant S7-1500H system is permitted for the ET 200SP R1.
Maximum configuration
• 64 ET 200SP I/O modules
• 1 m backplane bus (without interface module)
Maximum amount of I/O data
Gross data length (for input data and output data):
• 1440 bytes
The number of maximum net data lengths for input and output data depends on the number
and type of I/O modules used.
Calculation of the max. net data length:
The max. net data length is calculated according to the following formula:
Max. net data length = "Max. gross length" – "Total number of I/O submodules" – "Number of
mixed I/O modules (input and output data)" – "9 bytes for interface module and server
module"
The result of the calculation of the maximum net data length applies equally to input and
output data.
Interface Module IM 155-6 PN R1 (6ES7155-6AU00-0HM0)
Equipment Manual, 11/2022, A5E51160307-AA
connectors
Product overview
2.1 Properties
15

Advertisement

Table of Contents
loading

Table of Contents