Interrupts, error messages, diagnostics and system alarms
5.1 Status and error displays
RN/ER/MT LEDs on the interface module
Table 5- 1
Status and error displays of RN/ER/MT LEDs
LEDs
RN
ER
(RUN)
(ERROR)
Off
Off
On
On
On
On
Not
relevant
Flashes
Not
relevant
On
Not
relevant
Flashes
Not
Not
relevant
relevant
Flashes
Flashes
* PWR LED on (on the interface module): Check the backplane bus for short-circuit.
32
MT
(MAINT)
Missing or insufficient supply voltage
on interface module.
Off
Test of LEDs during startup: The three
LEDs light up simultaneously for
On
approximately 0.25 s.
RN/ER/MT LEDs are permanently on:
Hardware or firmware defective. Error
On
information will be determined and
stored retentively on the Flash
memory.
Not
Interface module is deactivated.
relevant
Interface module is not configured.
ET 200SP is starting up.
ET 200SP is being assigned
parameters.
Not
ET 200SP is currently exchanging data
relevant
with an IO controller.
Not
Group error and group error channels
relevant
The preset configuration does not
match the actual configuration of the
ET 200SP.
Invalid configuration states
Parameter assignment error in the I/O
module
A maintenance required is present,
that is, at least one maintenance event
On
has occurred.
The "Node flash test" is run (the LEDs
LK1 and LK2 of the PROFINET interface
Flashes
also flash).
Hardware or firmware defective (the
LEDs LK1 and LK2 of the PROFINET
interface do not flash).
Meaning
Interface Module IM 155-6 PN R1 (6ES7155-6AU00-0HM0)
Remedy
Check the supply voltage or turn it on at the
interface module.*
-
Do not disconnect the interface module from
the supply voltage while the LEDs are
permanently lit up. This process takes
between 20 s and 6 min.
Activate the interface module with the
configuration software or via the user
program.
Configure the interface module with the
configuration software.
-
-
Evaluate the diagnostics and eliminate the
error.
Check the design of the ET 200SP R1 to see
whether a module is missing or defective, or
whether a non-configured module is inserted.
You can find information on the hardware
configuration of the ET 200SP R1 in the
ET 200SP Distributed I/O System system
manual; section Application planning,
Hardware configuration.
Evaluate the display of the module status in
HW Config and eliminate the error in the
respective I/O module.
You can find more information in the section
Maintenance alarms (Page 41).
Restart the device by disconnecting and
reconnecting the supply voltage and read out
the service data as described in the manual.
Replace the interface module.
-
Equipment Manual, 11/2022, A5E51160307-AA