Interrupts, error messages, diagnostics and system alarms
5.3 Alarms
Diagnostic alarm
Channel
error
type
(CET)
Configuration error:
0x0602
Module parameter
'potential group'
incorrect or wrong
BaseUnit/TerminalBlo
ck on real
configuration slot
<slot>
Load voltage error:
0x0610
Missing voltage in
load group at slot
according channel
number
Redundancy error:
0x0630
Maintenance
demanded <internal
error code>
Redundancy error:
0x0630
Failure in BusAdapter
of partner module
*) Read the service data according to the description in the manual and send them to the SIEMENS Customer Support for
root cause analysis.
PROFINET IO
Another source of diagnostic events is the PROFINET basic technology in use. It generates
diagnostics messages containing coding that is already defined in the PROFINET IO Standard -
Application Layer Service Definition V2.2.
The actual scope of diagnostics used is dependent on the configuration and parameter
assignment.
You can download the standard if needed on the Internet (https://www.profibus.com) from
the home page of the PROFIBUS user organization.
40
Extended
Associated
Channel
value
Error
AddValue
Type
(ECET)
0x069F
Slot
0x6B0
-
0x06D0
ErrorCode
0x06D2
-
Meaning / Cause
The configured BaseUnit or
the terminal block does not
match the real configuration.
No supply voltage to the
load group.
There is a problem which
may lead to redundancy loss.
The BusAdapter of the
redundancy partner module
is not installed or is not
supported.
Interface Module IM 155-6 PN R1 (6ES7155-6AU00-0HM0)
Equipment Manual, 11/2022, A5E51160307-AA
Remedy
Check for suitable base unit or
terminal block.
Check the load supply voltage
of the modules.
Perform the operating
instructions described in the
manual. The interface
modules and the BaseUnit
should be replaced at the next
opportunity.
*)
Replace BusAdapter of partner
module.