Circuit diagrams
N
L
Neutral
Hot
Fuse
Service
Switch
T
T
L1
L2
C2
(L7248C1006)
B2
C1
B1
Becket NX Wiring Schematic -
With a L7248C1006 Aquastat –
1) Connect room thermostat or end switch wiring to the T T terminals of the L7248C Aquastat.
Note: DO NOT CONNECT ROOM THERMOSTAT TO THE "T T" TERMINALS OF THE R7184B OR 7505B PRIMARY CONTROL!
2) Connect 120 Vac power source to L1 on the L7248C aquastat.
3) Connect neutral source to L2 on the L7248C aquastat.
4) Connect the black wire in wire harness to B1 of the L7248C (the black wire on the R7184B or 7505B Primary Control).
5) Connect the white wire in wire harness to B2 of the L7248C (the white wire on the R7184B or 7505B Primary Control).
6) Connect the green wire in the wire harness to ground screw on the L7248C (the ground connection on the R7184B or 7505B Prima ry Control).
7) Install a jumper wire on the T T terminals of the R7184B or 7505B Primary Control.
*) Canadian installations: Install in series with start wire to the burner.
Fig. 50 Circuit diagram 3
52
Becket NX Burner Wiring
Thermostat,
aquastat, or end
switch,
Black wire
Honeywell
White wire
Operating
Aquastat
Ground
WMO-1*
Quick
Honeywell R7184B series Primary Control
connect plug
or Beckett Genisys 7505B Primary Control
Ground
Green wire
CAD
Cell
Burner Junction Box
Logano G115 WS US/CA – 6 720 813 418 (2019/09)
Red
A
Black
A
White
Violet
Blue
T
Orange
T
Yellow
Yellow
Field installed
jumper
Low Voltage – Field
installed
Field wiring
Factory wired