Product Description; Designated Use; Standards, Regulations And Directives; National Regulations - Buderus Logano G234X Installation And Service Instructions Manual

Gas central heating boilers
Table of Contents

Advertisement

2

Product Description

Danger of electric shock when the boiler is open.
Before opening the boiler:
▶ Disconnect the heating system from the electrical power supply via
the ON/OFF switch or the appropriate building fuse. It is not
sufficient just to switch off the controller. Power to the controller
must be disconnected.
▶ Take measures to ensure that the heating system cannot be
accidentally reactivated.
▶ Electrical work may be carried out only by qualified and certified
electricians.
Danger due to short-circuits
To prevent short circuits:
▶ only genuine Buderus wiring replacement parts.
▶ Do not attempt to operate an appliance if any part of it has been
under water.
▶ Replace any appliance that has been under water.
Risk of system damage due to contaminated combustion air supply
▶ Keep the combustion air free of corrosive substances, e.g.
halogenated hydrocarbons from painting operations or beauty
salons.
▶ Keep combustion air free from dust and lint (e. g. from nearby
laundry or agricultural operations).
▶ If clean room air is not available, fresh outdoor combustion air must
be provided.
Risk of system damage in the event of improper operation
▶ Use the boiler only for its intended purpose.
▶ Operate the boiler only if it has been installed and maintained per the
instructions provided in the Installation Manual.
▶ Do not attempt to operate an appliance if any part of it is not in
working order or is damaged.
▶ Use only original spare parts. The use of parts not supplied by the
manufacturer may cause damage to the boiler, other property and
personal injury. Also, boiler damage caused by the use of
unauthorized parts is not covered by the warranty.
▶ With sealed combustion appliances: do not cover or reduce the size
of air inlet and ventilation openings in doors, windows and walls.
▶ If draft-proof windows are installed, ensure an adequate supply of
combustion air.
Notice regarding regulations and legal requirements
▶ The installation must comply with all applicable national, state, and
local codes, rules, and regulations.
▶ The operator is responsible for the operational safety and regulatory
compliance of the heating system.
▶ In the Commonwealth of Massachusetts, the appliance must be
installed by a licensed plumber or gas fitter.
Instructing the owner/operator
▶ The installer must instruct the owner and operator on the
functionality of the components and the proper operation of the
boiler and the heating system.
▶ Upon completion of the installation, these instructions should be
handed to the owner and operator of the appliance.
▶ Inform the owner/operator that they must never carry out any
modifications or repairs.
4
2
Product Description
This installation and maintenance manual contains important
information for the safe and correct installation, initial commissioning,
and maintenance of this boiler.
The Logano G234X floor-standing gas boiler is generally referred to
below as a boiler.
The installation and maintenance manual is provided for technicians
who have been trained and have experience in working with heating
systems and oil- and gas-fired installations.
▶ Use the boiler only in the combinations and with the accessories and
spare parts that are specified in the installation and maintenance
instructions.
▶ Other combinations, other accessories and spare parts must only be
used if they are specifically designed for the intended application and
do not affect the system performance and the safety requirements.
2.1

Designated use

The boiler is designed for heating central heating system water and
indirect provision of domestic hot water (e.g. in a hot water storage
tank) in residential buildings or apartment buildings. Any other purpose
is considered improper use.
2.2

Standards, regulations and directives

For the installation and operation of the heating system,
observe all country-specific standards and guidelines!
2.2.1

National regulations

The design and mode of operation of this boiler comply with the
American National Standard ANSI Z21.13/CSA4.9, latest edition for
Gas-Fired Low-Pressure Steam and Hot Water Boilers.
Other confirmed approvals and certifications are indicated by stickers
on the boiler.
Installation of the boiler must comply with all applicable codes and
regulations imposed by the national, state or local authorities and
bodies. The relevant authorities and regulatory bodies must be informed
before installation starts.
If no specific requirements are defined, the latest edition of the National
Fuel Gas Code ANSI Z223.1/NFPA 54 must be complied with for all
installations in the USA. Installations in Canada must comply with the
latest edition of the Installation Code for Gas Burning Appliances and
Equipment, CAN/CSA-B.149. Where required by local authorities, the
system must comply with the American Society of Mechanical Engineers
Safety Code for Controls and Safety Devices for Automatically Fired
Boilers (ASME CSD-1).
Carbon monoxide detectors must be installed as specified by the local
regulations. Boiler requires yearly maintenance.
2.2.2

Boiler operating conditions

Maximum boiler temperature:
Maximum operating pressure:
The hot water piping system must comply with all applicable codes and
regulations. If an existing boiler is being replaced, the entire hot water
piping system must be inspected to ensure that it is in suitable condition
to assure safe operation.
Logano G234X – 6 720 811 233 (2014/05)
210 °F (99 °C)
58 psi (4 bar)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents