Unit Weight and Rigging

WARNING
Heavy Objects!
Failure to follow instructions below or properly lift unit
could result in unit dropping and possibly crushing
operator/technician which could result in death or
serious injury, and equipment or property-only damage.
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables (chains or slings) may
not be of the same length. Adjust as necessary for even
unit lift.
AVERTISSEMENT
Objets lourds!
Le non-respect des instructions ci-dessous ou un levage
inapproprié de l'unité peut provoquer sa chute voire
écraser l'opérateur/le technicien, ce qui peut
occasionner des blessures graves voire mortelles, et
éventuellement endommager l'équipement ou
provoquer des dégâts matériels. Assurez-vous que
l'équipement de levage utilisé est adapté au poids de
l'unité à soulever. Chaque câble (chaîne ou élingue),
crochet ou manille utilisé pour le levage de l'unité doit
être assez robuste pour supporter le poids total de
l'unité. Les câbles, chaînes ou élingues de levage ne
doivent pas être de longueur identique. Procédez au
réglage afin de soulever l'unité de manière équilibrée.

Unit Weight

Table 1.
Typical unit weight, center of gravity, and corner weights (percentage of total weight) - air cooled units without
powered exhaust or ERV
Weight (lbs)
Model Number
Min
OADG010
2209
OANG070
2209
OADG015
2209
OADG012
2430
OADG017
2430
OADG020
6220
OANG040
6220
OANG045
6220
OANG050
6565
OANG055
6565
OANG060
6881
OANG080
7038
(a) Refer to
Figure 21, p. 26
and
OAU-SVX006E-EN
Center of Gravity (in.)
Max
Length
3578
54
3578
54.2
3578
53.3
3585
54.1
3585
53.4
8111
87.2
8111
87.2
8111
87.2
8505
91.4
8505
91.4
8883
96.0
9058
95.6
Figure 22, p. 26
for corner locations.
Improper Unit Lift!
Failure to properly lift unit could result in unit dropping
and possibly crushing operator/technician which could
result in death or serious injury, and equipment or
property-only damage. Test lift unit approximately
24 inches to verify proper center of gravity lift point. To
avoid dropping of unit, reposition lifting point if unit is
not level.
AVERTISSEMENT
Levage inapproprié de l'unité!
Le non-respect des instructions ci-dessous ou un levage
inapproprié de l'unité peut provoquer sa chute voire
écraser l'opérateur/le technicien, ce qui peut
occasionner des blessures graves voire mortelles, et
éventuellement endommager l'équipement ou
provoquer des dégâts matériels. Faites un test de
levage de l'unité d'environ 60 cm (24 po) afin de vérifier
que le point de levage correspond au centre de gravité
de l'appareil. Pour éviter une chute de celle-ci, ajustez
son point de levage si elle n'est pas à l'horizontale.
Corner weight (% of total weight)
Width
Corner A
Corner B
41.1
20
41.7
19
41.1
19
41.3
23
41
21
50.1
24
50.1
24
50.1
24
50.2
24
50.2
24
50.5
24
50.7
24
WARNING
(a)
Corner C
Corner D
15
36
15
36
16
36
11
39
14
37
26
26
26
26
26
26
26
26
26
26
26
26
26
26
29
30
29
26
28
24
24
24
24
24
24
24
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Horizon oang series

Table of Contents