System Configuration and Pre-Start
Table 8.
Chart of analog and binary input/output (continued)
#
BACnet Point Name
Hot Gas Reheat Valve
AO-01
Command
Supply Fan Speed
AO-02
Command
Compressor Speed
AO-03
Command Circuit 1
Exhaust Fan Speed
AO-04
Output Command
Outdoor Air Damper
AO-05
Position Command
Energy Recovery
AO-06
Outdoor Air Bypass
Position Command
Condenser Fan Speed
AO-07
Command
Compressor Speed
AO-08
Command Circuit 2
Chilled Water Valve
AO-09
Command
Energy Recovery Wheel
Speed
AO-10
Command
Heating Output
AO-11
Command
Second Stage
Condenser Fan Speed
AO-12
Command
Energy Recovery
Exhaust Air Bypass
AO-13
Position Command
Occupied Cooling
AV-01
Setpoint
Occupied Heating
AV-02
Setpoint
Heat Pump Disable
AV-04
Temperature
Dehumidification
AV-05
Temperature Active
AV-07
Space Humidity Active
AV-08
Space Humidity BAS
Outdoor Air Dewpoint
AV-10
Enable Setpoint
AV-11
Outdoor Air Dewpoint
Exhaust Fan Tracking
AV-12
Offset Setpoint
42
Write
Default
Range
0–100
0–100
0–100
0–100
0–100
0–100
0–100
0–100
0–100
0–100
0–100
0–100
0–100
72°F
55–85
70°F
55–85
25°F
0–60
-58–482
0–100
0–100
55°F
45–100
-10–150
0.9
0–150
Units
Description
%
Analog hot gas reheat output.
%
Supply fan speed output.
Speed control for circuit 1 digital scroll or variable
speed
%
compressor.
%
Exhaust fan speed output
Position command for outdoor air damper. Return
air
%
damper position is inverse to this output.
Analog output for modulating ERV outdoor air
%
bypass.
%
Analog condenser fan speed command.
Speed control for circuit 1 digital scroll or variable
speed
%
compressor.
Analog chilled water actuator valve output
%
command.
%
Analog ERV VFD command.
Analog heating output command. Modulating
burner only
%
for gas heat.
Analog condenser fan speed command for the
second
%
stage.
Analog output for modulating ERV exhaust air
%
bypass.
°F
Space cooling setpoint used in occupied mode.
°F
Space heating setpoint used in occupied mode.
Heat pump operation is disabled when the outdoor
°F
air
temperature falls below this setpoint.
Temperature reading for dehumidificaiton. For OAN
Rev. 6 cabinets this is discharge air dewpoint, all
°F
other it's indoor
coil leaving temperature.
%
Actively used space relative humidity.
Communicated space relative humidity. Takes
%
priority over
hardwired input when put In Service.
°F
Setpoint used to put the unit into dehumidification.
Dewpoint of the outdoor air. This point is calculated
within
°F
the program.
Setpoint used to track with the supply fan speed.
Factory default is Out of Service. When put In
%
Service it takes priority over other exhaust fan
control schemes.
OAU-SVX006E-EN