Trane Horizon OADG Series Installation, Operation And Maintenance Manual page 45

Outdoor air unit, indirect fired gas/electric heat/air source heat pump
Table of Contents

Advertisement

Table 8.
Chart of analog and binary input/output (continued)
#
BACnet Point Name
Outdoor Air Enthalpy
AV-68
Active
Outdoor Air Flow
AV-71
Setpoint BAS
Return Air Enthalpy
AV-72
Active
Supply Fan Air Flow
Minimum Setpoint
AV-74
Active
Outdoor Air
AV-75
Temperature BAS
Outdoor Air
AV-76
Temperature Active
Dehumidification
AV-77
Temperature Setpoint
Active
Outdoor Air Humidity
AV-81
BAS
Outdoor Air Humidity
AV-82
Active
Space Humidity
AV-87
Setpoint
AV-88
Condenser Fan P-Gain
BI-01
Supply Fan Status
BI-02
Emergency Stop
BI-03
Final Filter Status
BI-04
Occupancy Input
Outdoor Air Damper
BI-05
End Switch
Heat On Off Status
BI-06
Local
Exhaust Damper End
BI-07
Switch
Outdoor Coil Water
BI-08
Flow Status
Outdoor Coil Water Low
BI-09
Temperature Switch
Condensate Detection
BI-10
Input
BI-11
Indoor Coil Frostat
OAU-SVX006E-EN
Write
Default
Range
0–25000
0–25000
-40–135
-100–200
48°F
38–75
0.5
0-100
0.45
0-100
0.45
0–100
4
0–10
0=Off
1=On
0=Normal
1=ESTOP
0=Clean
1=Clogged
0=Unocc.
1=Occupied
0=Not
Proven
1=Proven
0=Off 1=On
0=Not
Proven
1=Proven
0=Off
1=On
0=Open
1=Closed
0=Normal
1=InAlarm
0=Clean
1=Frost
System Configuration and Pre-Start
Units
Description
BTU/lb Actively used outdoor air enthalpy.
cfm
Setpoint to modulate the dampers.
BTU/lb Actively used outdoor air enthalpy.
Actively used setpoint. Controlled by program from
cfm
minimum setpoints for heating and cooling mode.
°F
Optional communicated outdoor air temperature.
°F
Actively used outdoor air temperature.
°F
Actively used setpoint during dehumidification.
Optional communicated outdoor air relative
%
humidity.
%
Actively used outdoor air relative humidity.
Setpoint used to calculate Space Dewpoint
%
Setpoint.
Pgain used to control condenser fans
Status of the supply fan using a differential
pressure
switch.
Auto Reset. Shuts the unit down.
Auto Reset. Notificaiton when differential
presssure switch closes (adj. range) for the filters
in front of the indoor coil.
Dry contact input for Occupancy Status. Wired to
field wiring terminal strip OAUTS-7 & 8. To use MV-
01 keep
factory installed jumper in place.
End switch for outdoor air damper.
Auto Reset (4 hours). Occurs when there is a call
for heat but the heat status relay is not energized.
The heat is cycled three times and then locked out
for four hours
before retrying.
End switch for isolation dampers for the exhaust
fan.
Water flow status for outdoor water coil using a
differential
pressure switch.
Low temperature safety switch for outdoor water
coil.
Auto Reset.
Auto Reset.
45