Filter Installation; Field Installed Power Wiring - Trane Horizon OADG Series Installation, Operation And Maintenance Manual

Outdoor air unit, indirect fired gas/electric heat/air source heat pump
Table of Contents

Advertisement

Installation
Table 4.
Chilled water pipe chase location, in. (cm)
Unit
A
OAD
64.25 (163.2) 30.00 (76.2)
OAN
92.64 (235.3) 30.00 (76.2)
Table 5.
Chilled water connection size (MPT-in.)
Unit Size
OAD, 4-row
OAD, 6-row
OAN, 4-row
OAN, 6-row

Filter Installation

Each unit ships with 2-in. (5.1-cm) permanent filters (mist
eliminators) installed in the air inlet hood. The quantity of
filters is determined by unit size. Access to the filters is
through the hinged filter access panel on the air intake
hood. In addition to the filters in the intake hood, there is
a separate bank of filters accessible through the
evaporator coil compartment door. Filter type, size, and
quantity are determined by selected filter option and unit
size.
Note: Do not operate the unit without filters.

Field Installed Power Wiring

WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
AVERTISSEMENT
Câblage sur site et mise à la terre corrects
nécessaires!
Le non-respect de la réglementation peut entraîner des
blessures graves, voire mortelles. Il est IMPÉRATIF de
confier l'ensemble du câblage sur site à un électricien
qualifié. Un câblage sur site mal installé ou mal mis à la
terre constitue des risques D'INCENDIE et
D'ÉLECTROCUTION. Pour éviter ces risques, il est
IMPÉRATIF de respecter les obligations en matière de
pose de câblage sur site et de mise à la terre tel que
stipulé dans les règles du NEC et dans les
réglementations électriques locales/nationales.
An overall dimensional layout for the standard field
installed wiring entrance into the unit is illustrated in
32
B
C
D
18.00 (45.7)
3.50 (8.9)
18.00 (45.7)
2.81 (7.1)
MPT-in. (cm)
1.5 (3.8)
2.0 (5.1)
2.5 (6.3)
3.0 (7.6)
Figure 38, p.
33. To ensure that the unit's supply power
wiring is properly sized and installed, refer to the following
guidelines.
Figure 36. OAD power entrance
Auxiliary Power Disconnect
Main Power Disconnect
Main Power Entrance to Unit
Figure 37. OAN power entrance
A
AUXILIARY POWER DISCONNECT
MAIN POWER DISCONNECT
MAIN POWER ENTRANCE TO UNIT
DETAIL A
OAU-SVX006E-EN