Trane Horizon OADG Series Installation, Operation And Maintenance Manual page 48

Outdoor air unit, indirect fired gas/electric heat/air source heat pump
Table of Contents

Advertisement

System Configuration and Pre-Start
Table 8.
Chart of analog and binary input/output (continued)
#
BACnet Point Name
Unoccupied Dehumid
BV-40
Mode
Energy Recovery Frost
BV-41
Avoidance Status
BV-43
Ventilation Mode
BV-44
Free Cooling Mode
Economizer Control
BV-45
Type
Mixed Air Low Limit
BV-49
Active
Defrost Mode Heat
BV-57
Enable
Compressor Heating
BV-61
Allowed
Compressor Cooling
BV-62
Allowed
BV-63
Circuit 2 Status
Compressor Low
BV-64
Ambient Lockout Active
MV-01
Occupancy Request
MV-02
Occupancy Status
Heat Cool Mode
MV-03
Request
MV-04
Heat Cool Mode Status
Discharge Air
MV-05
Temperature Setpoint
Source Status
Emergency Override
MV-06
BAS
Space Temperature
MV-07
Setpoint Source Status
Dehumidification
Temperature Source
MV-08
Status
MV-09
Heat Type
48
Write
Default
Range
0=Off
1=On
0=Normal
1=Active
0=Off 1=On
0=Off
1=On
0=DryBulb
Enthalpy
1=Enthalpy
0=Normal
1=Active
0=Off 1=On
0=Allowed
1=Not
Allowed
0=Allowed
1=Not
Allowed
0=Off
1=On
0=Active
1=Not
Active
1
Units
Description
Dehumidification mode status during unoccupied.
Status indicating when actively bypassing or
slowing down energy recovery wheel to prevent
frost accumulation.
Status for ventilation mode, locking out heating
and cooling.
Status for free cooling mode, using outdoor air
temperature to maintain setpoint.
Used to switching between dry bulb or enthalpy
economizer.
Auto-Reset:
Status indicating supplemental heat during
outdoor coil defrost mode.
Active status on whether heat pump is allowed.
Active status on whether cooling is allowed.
Feedback status on the circuit 1 refrigeration.
Status indicating that the unit is calling for cooling
but the compressors are locked out due to low
ambient
temperature.
1 = Occupied
2 = Unoccupied
3 = Occupied Bypass 4 = Occupied Standby 5 =
Auto
1 = Occupied
2 = Unoccupied
3 = Occupied Bypass 4 = Occupied Standby
1 = Auto
2 = Heat
3 = Morning Warm-up 4 = Cool
7 = Off
10 = Fan Only
11 = Economizing
15 = Dehumidify
See Heat Cool Mode Request (MV-03)
1 = Discharge Air Cooling Setpoint BAS 2 =
Discharge Air Heating Setpoint BAS
3 = Discharge Air Temperature Setpoint BAS
4 = Reset for Space Comfort Control
1 = Normal
6 = Fire
1 = Occupied Heating Setpoint 2 = Occupied
Cooling Setpoint
3 = Thumbwheel (Space Temperature Setpoint
Local)
4 = Space Temperature Setpoint BAS
1 = Discharge Air Dewpoint
2 = Indoor Coil Coil Leaving Temperature
Factory set heat type.
OAU-SVX006E-EN