Trane Horizon OADG Series Installation, Operation And Maintenance Manual page 44

Outdoor air unit, indirect fired gas/electric heat/air source heat pump
Table of Contents

Advertisement

System Configuration and Pre-Start
Table 8.
Chart of analog and binary input/output (continued)
#
BACnet Point Name
Supply Fan Air Flow
AV-41
Active
Space CO2
AV-42
Concentration BAS
Discharge Air
AV-43
Temperature Setpoint
Minimum
AV-44
Heat Capacity
Discharge Air
Temperature Setpoint
AV-45
Maximum
Duct Static Pressure
AV-46
Setpoint BAS
Outdoor Air Damper
Maximum Position
AV-47
Setpoint
Outdoor Air Damper
Minimum Position
AV-48
Setpoint
Space CO2
AV-50
Concentration Setpoint
AV-51
Cool Control Pgain
AV-52
Cooling Capacity
Exhaust Fan Air Flow
AV-54
Active
Direct Fired Profile
AV-55
Width
Return Duct/Space
AV-56
Pressure Setpoint
Exhaust Fan Air Flow
AV-57
Setpoint
Supply Fan Air Flow
Minimum Setpoint -
AV-59
Cooling Mode
AV-61
Heat Control Pgain
Space CO2
AV-62
Concentration Active
Heat Pump Fail Switch
AV-63
Point
Duct Static Pressure
AV-64
BAS
Duct Static Pressure
AV-65
Active
Discharge Air
AV-66
Temperature Setpoint
Active
Discharge Air
AV-67
Temperature Setpoint
BAS
44
Write
Default
Range
0–26000
50°F
40–65
0–100
120°F
80–120
1.5
-1–6
1
0–100
0–100
500
0–3000
4
0–12
0–500
0–26000
6–28
0.5
-1–3
0–25000
0
4
0–10000
-58–482
-6–6
-6–6
38–130
55°F
40–125
Units
Actively used supply airflow. Calculated using the
supply
cfm
fan piezo pressure.
ppm
Communicated space CO2 conditions.
Setpoint used to limit the discharge air
°F
temperature reset.
%
Primary heating source capacity.
Setpoint used to limit the discharge air
°F
temperature reset.
Setpoint used to control supply fan to static
in.H
O
2
pressure.
Setpoint used to limit the outdoor air damper
position
%
during all operation.
Setpoint used to limit the outdoor air damper
position
%
during all operation.
ppm
Setpoint used to control the outdoor air damper.
Pgain used to control the compressors.
%
Active cooling capacity of the unit.
Actively used exhaust airflow. Calculated using the
supply
cfm
fan piezo pressure.
Width of the profile opening for direct fired heaters.
Used
to calculate air flow.
Setpoint used for exhaust fan static pressure
in.H
O
2
control.
Setpoint used for constant volume exhaust fan
cfm
control.
Setpoint used for supply fan during cooling or heat
pump
cfm
operation.
0–6
Pgain used to control primary heat.
ppm
Actively used space CO2 conditions.
Outdoor air temperature at which the heat pump
failed to
°F
meet setpoint.
Communicated duct static pressure. Factory
defaulted Out
in.H
O
2
of Service. When put In Service it takes priority
over hardwired input.
in.H
O
Actively used duct static pressure.
2
Actively used discharge air temperature setpoint.
For
°F
Space Control and Single Zone VAV this is reset
within the program.
Communicated discharge air temperature
setpoint. Factory default Out of Service. When put
°F
In Service it replaces Discharge Air Cooling and
Heating Setpoints.
Description
OAU-SVX006E-EN