Mitsubishi Electric PUMY-P36NKMU3 Technical & Service Manual page 97

Hide thumbs Also See for PUMY-P36NKMU3:
Table of Contents

Advertisement

Check code
7102
(EF)
Abnormal points and detection methods
When the connected indoor units exceed the limit, a check code <7102> is
displayed.
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Check whether the connecting unit
exceeds the limit or not.
Does it exceed the limit?
Check if at least 1 indoor unit is connected.
Is an indoor unit connected?
OCH733
Connecting excessive number of units
Diagnosis
No
Yes
Causes and checkpoints
Connecting more indoor units than the limit.
Abnormal if connecting status does not comply with the
following limit;
Connectable up to 11 units for P36 and HP36, 12 units
for P48, HP48 ,P60
Connect at least 1 indoor unit (Abnormal if connected
none).
Connectable only 1 ventilation unit
Connect less number of units than the
Yes
limit.
The model code of the connected indoor
unit can be displayed by an operation of
SW1 on the outdoor unit.
No
Check whether the M-NET line to the
indoor unit is connected or not.
97
Remedy
Connect indoor unit.