7-2. Special Function Operation and Settings for M-NET Remote Controller
For the detailed procedure of "group settings" and "paired settings", refer to the remote controller's manuals.
7-3. REFRIGERANT SYSTEM DIAGRAM
Refrigerant piping specifications <dimensions of flared connector>
Capacity
Indoor unit
Outdoor unit
PUMY-P36NKMU3
PUMY-P48NKMU3
Service port
Strainer
Refrigerant Gas pipe
Ball valve
Thermistor (TH2)
<Hic pipe>
Stop valve
Refrigerant
Liquid pipe
Service port
Capillary tube for oil separator [inch(mm)]: ø 0.098 o ø 0.031 o L39.37 ( ø 2.5 o ø 0.8 o L1000)
OCH733
P04, P05, P06, P08, P12, P15, P18
P24, P27, P36, P48, P54
P72
P36, P48, HP36, HP48
P60
PUMY-P36NKMU3-BS
PUMY-P48NKMU3-BS
4-way valve
Check valve
<Low pressure>
Thermistor (TH6)
<Suction pipe>
Low pressure
sensor(63LS)
Restrictor
valve
Accumulator
HIC
Strainer
LEV-B
Strainer
Item
Liquid piping
1/4 <ø6.35>
3/8 <ø9.52>
3/8 <ø9.52>
3/8 <ø9.52>
3/8 <ø9.52>
Check valve
<High pressure>
Solenoid
Oil separator
valve (SV1)
High pressure
Strainer
sensor (63HS)
Capillary
tube
High pressure
switch (63H)
Strainer
Thermistor (TH4)
<Compressor>
Compressor
Strainer
LEV-A
37
Unit: inch <mm>
Gas piping
1/2 <ø12.7>
5/8 <ø15.88>
3/4 <ø19.05>
5/8 <ø15.88>
3/4 <ø19.05>
Refrigerant flow in cooling
Refrigerant flow in heating
Thermistor (TH7)
<Ambient>
Distributor
Thermistor (TH3)
<Outdoor liquid pipe>
Strainer