Check code
1302
(UE)
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Continued from the previous page.
Is the resistance detected?
Disconnect the indoor LEV wiring to check
the resistance.
Is the resistance detected?
Check the voltage(*) and appearance of
the indoor controller board.
Is the voltage normal?
Is it free from any trace of over-
heating or burning?
Check the resistance of SV1.
Continue to the next page.
OCH733
High pressure trouble
Diagnosis
No
Yes
No
Yes
*For the voltage, refer to "8-8.HOW
TO CHECK THE COMPONENTS".
Yes
Replace the indoor LEV.
Replace the indoor controller board.
No
55
Chart 3 of 4
Remedy
Replace the TH7.