2-3. SYSTEM SPECIFICATIONS
(1) Outdoor Unit
Service Ref.
Capacity
Cooling (kBtu/h)
Heating (kBtu/h)
Compressor (kW)
Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling
Indoor
D.B. 80°F/W.B. 67°F: [D.B. 26.7°C/W.B. 19.4°C]
Outdoor D.B. 95°F/W.B. 75°F: [D.B. 35°C/W.B. 23.9°C]
Heating
Indoor
D.B. 70°F/W.B. 60°F: [D.B. 21.1°C/W.B. 15.6°C]
Outdoor D.B. 47°F/W.B. 43°F: [D.B. 8.3°C/W.B. 6.1°C]
(2) Method for identifying MULTI-S model
Outdoor unit <When using model 48 >
PU M Y - H P 48 N K M U 1 - BS
Outdoor unit
MULTI-S
Frequency
conversion
controller
Hyper-Heating
INVERTER
Indicates equivalent
to Cooling capacity
(3) Operating temperature range
Indoor-side intake air temperature
Outdoor-side intake air temperature
Notes:
D.B. : Dry Bulb Temperature
W.B. : Wet Bulb Temperature
*
1
50 to 115°F [10 to 46°C] D.B. : When connecting PKFY-P06NBMU, PKFY-P08NHMU, PFFY-P06/08/12NEMU,
PKFY-P04/06/08/12NLMU and PFFY-P06/08/12NRMU type indoor unit.
*
2
5 to 115°F [−15 to 46°C] D.B.: When using an optional air protect guide.
However, this condition does not apply to the indoor units listed in *1.
OCH733
PUMY-P36NKMU3
PUMY-P36NKMU3-BS
PUMY-HP36NKMU1
36.0
42.0
2.8
Sub-
number
UL model
Refrigerant
M-NET
R410A
control
Outdoor unit
model type
Power supply
N: 208/230 V AC 60 Hz
W.B. 59 to 75°F [15 to 24°C]
D.B. 23 to 115°F [−5 to 46°C]*
PUMY-P48NKMU3
PUMY-P48NKMU3-BS
PUMY-HP48NKMU1
48.0
54.0
Salt proof
type
Cooling
, *
1
9
PUMY-P60NKMU3
PUMY-P60NKMU3-BS
3.3
Heating
D.B. 59 to 81°F [15 to 27°C]
2
W.B. −13 to 59°F [−25 to 15°C]
60.0
66.0
4.1