Mitsubishi Electric PUMY-P36NKMU3 Technical & Service Manual page 135

Hide thumbs Also See for PUMY-P36NKMU3:
Table of Contents

Advertisement

Method of Combined Branching of Lines and
Headers
Connection Examples
(Connecting to 5 Indoor Units)
Total Piping Length
Permissible
Farthest Piping Length
Length
Farthest Piping Length After First Branch
High/Low Difference in Indoor/Outdoor Section
Permissible High/
Low Difference
High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Piping
(1) Section From Outdoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d,e)
(3) Section From Branch to
Branch (B,C)
Select the size from the table to the right.
Additional refrigerant charge
OCH733
A
A
B
A+B+C+a+b+c+d+e is 492 ft [150 meters]
(L)
A+B+b is 262 ft [80 meters]
(R)
B+b is 100 ft [30 meters]
(H)
164 ft [50 meters] (If the outdoor unit is lower, 131 ft [40 meters] or less)
(h)
49 ft [15 meters]
Please select branching kit, which is sold separately, from the table below.
(The kit comprises sets for use with liquid pipes and for use with gas pipes.)
Branch Joint
CMY-Y62-G-E
(1) Refrigerant Piping Diameter In Section
From Outdoor Unit to First Branch
(Outdoor Unit Piping Diameter)
Model
Each
Section of
PUMY-P60NKMU3
Piping
(3) Refrigerant Piping Diameter In Section
From Branch to Branch
Liquid Line (inch [mm])
3/8 [ø9.52]
Refer to the same section in the previous page.
135
Note: Pipe re-branching after the header branching
is not possible.
C
c
d
3
4
B
D
D
L
R
b
a
2
C
D
1
Branch Header (4 branches)
CMY-Y64-G-E
Piping Diameter (inch [mm])
Liquid Line
3/8 [ø9.52]
3/4 [ø19.05]
Gas Line
Gas Line (inch [mm])
3/4 [ø19.05]
E
F
e
5
D
A
Outdoor unit
B
First branching (branching
joint)
C
Branching joint
D
Indoor unit
D
E
Branching header
F
Blind caps
Branch Header (8 branches)
CMY-Y68-G-E
(2) Refrigerant Piping Diameter In Section
From Branch to Indoor Unit
(Indoor Unit Piping Diameter)
Model number
Piping Diameter (inch [mm])
Liquid Line
1/4 [ø6.35]
18 or lower
Gas Line
1/2 [ø12.7]
Liquid Line
3/8 [ø9.52]
24 to 54
Gas Line
5/8 [ø15.88]
Liquid Line
3/8 [ø9.52]
72
Gas Line
3/4 [ø19.05]

Advertisement