Mitsubishi Electric PUMY-P36NKMU3 Technical & Service Manual page 148

Hide thumbs Also See for PUMY-P36NKMU3:
Table of Contents

Advertisement

OPERATING PROCEDURE
14. Removing the accumulator
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electrical parts box. (See Photo 5)
(4) Remove the valve bed. (See procedure 8 (4))
(5) Remove the cover panel (front). (Refer to procedure 8(5))
(6) Remove the cover panel (rear) (Refer to procedure 8(6))
(7) Remove the side panel (R). (Refer to procedure 8 (7))
(8) Recover refrigerant.
(9) Remove 2 welded pipes of accumulator inlet and outlet.
(10) Remove 2 accumulator leg fixing screws (4 × 10). (See
Photo 16)
Note: Recover refrigerant without spreading it in the air.
15. Removing the reactor (DCL)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electrical parts box (See photo 5)
(4) Remove 6 screws (4 x 10) for reactors to remove the
reactors. (See Figure 3)
OCH733
PHOTOS/FIGURES
Photo 15
Outlet
Photo 16
Compressor
(MC)
Separator
Separator
fixing screw
Figure 3
Screws for
reactors
148
Inlet
Accumulator
Accumulator
Accumulator
leg
Accumulator
Compressor
leg fixing
fixing nuts
screws
Reactors

Advertisement

Table of Contents
loading

Table of Contents