Mitsubishi Electric PUMY-P36NKMU3 Technical & Service Manual page 132

Hide thumbs Also See for PUMY-P36NKMU3:
Table of Contents

Advertisement

Method of Combined Branching of Lines and
Headers
Connection Examples
(Connecting to 5 Indoor Units)
Total Piping Length
Permissible
Farthest Piping Length
Length
Farthest Piping Length After First Branch
High/Low Difference
Permissible High/
Low Difference
in Indoor/Outdoor Section
High/Low Difference in Indoor/Indoor Section
Selecting the Refrigerant Branch Kit
Select Each Section of Refrigerant Piping
(1) Section From Outdoor Unit
to First Branch (A)
(2) Sections From Branch to
Indoor Unit (a,b,c,d,e)
(3) Section From Branch to
Branch (B,C)
Select the size from the table to the right.
Additional refrigerant charge
OCH733
A
Note: Pipe re-branching after the header branching
A
B
A+B+C+a+b+c+d+e is 984 ft [300 meters]
(L)
A+B+b is 492 ft [150 meters]
(R)
B+b is 98 tf [30 meters]
The outdoor unit is upper: 164ft [50m] or less
(H)
The outdoor unit is lower: 131ft [40m] or less (98ft [30,] or less if PKFY-P06NBMU, PKFY-P08NHMU,
PKFY-P04/06/08/12NLMU, PFFY-P06/08/12NEMU, and PFFY-P06/08/12NRMU are included.)
(h)
49 ft [15 meters]
Please select branching kit, which is sold separately, from the table below.
(The kit comprises sets for use with liquid pipes and for use with gas pipes.)
Branch Joint
CMY-Y62-G-E
(1) Refrigerant Piping Diameter In Section
From Outdoor Unit to First Branch
(Outdoor Unit Piping Diameter)
Model
Each
Section of
PUMY-P36NKMU3
Piping
PUMY-P48NKMU3
PUMY-HP36NKMU1
PUMY-HP48NKMU1
(3) Refrigerant Piping Diameter In Section
From Branch to Branch
Liquid Line (inch [mm]) Gas Line (inch [mm])
3/8 [ø9.52]
Refer to the same section in the previous page.
is not possible.
C
c
d
3
4
5
B
D
D
L
R
b
a
2
C
D
D
1
Branch Header (4 branches)
CMY-Y64-G-E
(2) Refrigerant Piping Diameter In Section
Piping Diameter (inch [mm])
Model number
Liquid Line
3/8 [ø9.52]
18 or lower
Gas Line
5/8 [ø15.88]
5/8 [ø15.88]
132
E
F
e
A
Outdoor unit
B
First branching (branching
D
joint)
C
Branching joint
D
Indoor unit
E
Branching header
F
Blind caps
Branch Header (8 branches)
CMY-Y68-G-E
From Branch to Indoor Unit
(Indoor Unit Piping Diameter)
Piping Diameter(inch [mm])
Liquid Line
1/4 [ø6.35 ]
Gas Line
1/2 [ø12.7]
Liquid Line
3/8 [ø9.52]
24 to 54
Gas Line
5/8 [ø15.88]