Error mes-
Description
sage
(hex)
0xE1FE0600
Error in transponder memory
The transponder has never been written to or has lost the contents of its memory due to battery
failure.
Possible causes / action to be taken:
Replace transponder (if battery bit is set).
Re-initialize transponder.
RF300: Data storage was not completed correctly for the semaphore procedure.
0xE1FE0700
Password error
RF300: ECC error
Possible causes:
The bit error could not be corrected.
Transponder data has been lost (transponder defective).
The transponder was not initialized with the ECC driver.
The EEPROM memory of the transponder has reached its end of life and the data has been
lost.
The transponder (with FRAM memory) has been stored too hot and has lost information.
It is possible that the transponder can still be used after initialisation.
0xE1FE0800
The transponder in the antenna field does not have the expected UID / EPC ID or has no UID / EPC
ID.
0xE1FE0900
The command is not supported by the transponder.
0xE1FE0A00
The transponder is read/write-protected.
0xE1FE8100
The transponder is not responding.
0xE1FE8200
The transponder password is incorrect. Access is denied.
0xE1FE8300
The verification of the written transponder data has failed.
Possible causes:
Transponder is defective.
Transponder is in the limit area.
0xE1FE8400
General transponder error
Contact Support if needed.
0xE1FE8500
The transponder has too little power to execute the command.
Possible causes:
Transponder is in the limit area.
The transmission/radiated power of the reader or antenna is too low.
Ident profile, Add-on instruction for Rockwell systems
Function Manual, 07/2020, C79000-G8976-C410-04
5.1 Error messages from the Ident profile / Ident instructions
Diagnostics and error messages
105