Note
Damage to the line supply cable due to excessively short stripped length
If the specified insulated conductor and stripped lengths are not complied with, single wires can
be damaged or shield contact prevented.
• Comply with the specified insulated conductor and stripped lengths.
Note
Cables for UL applications
Use only 75 °C copper cables for UL applications.
Table 6-14
End sleeves and recommended cable cross-sections
When crimped, end sleeves must not exceed the maximum dimensions of 5.3 x 5.3 mm
1)
(0.21 x 0.21 in), as otherwise single wires will not be able to be inserted or removed.
6.2.1.3
Crimping conductor end sleeves
The following crimping tool is available from Weidmüller to crimp conductor end sleeves
(www.weidmueller.com).
• Type PZ 6/5, article number 9011460000
Figure 6-6
Booksize power units
Equipment Manual, 01/2022, 6SL3097-6AC30-0BP0
End sleeves and recommended cable cross-sections
AWG 10
10 mm
16 mm
AWG 6
Crimp shape PZ 6/5
6.2 Accessories for Smart Line Modules
Dimensions of the terminal openings
6 mm
2
2
AWG 8
2
1)
Accessories