Power-Supply Module Installation
Figure 3-14
Connect the input power as described in the
Step 5
Wiring the DC-Input Power Source
Before you wire the DC-input power source, review the warnings in this section and this information:
Warning
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that
the protective device is rated not greater than:
10 A Statement 1005
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring.
Warning
Statement 1022
Only trained and qualified personnel should be allowed to install or replace this equipment.
Warning
Statement 103
Connect the unit only to a DC-power source that complies with either DC mains or Safety Extra-Low
Caution
Voltage (SELV) requirements in IEC 60950 based safety standards. Do not connect to a hazardous
voltage source.
The DC-power-supply voltage should be within the range that you select on the DC-power-supply
Caution
voltage switch, either –36 to –72 VDC or +18 to +36 VDC. If the supply voltage is not in this range, the
switch might not operate properly or might be damaged.
Cisco ME 3400E Ethernet Access Switch Hardware Installation Guide
3-12
DC-Voltage Selector
P S U O K
+ 2 4 V - 4 8
V
Chapter 3
Installing and Removing AC- and DC-Power-Supply Modules
"Wiring the DC-Input Power Source"
section.
OL-16447-01