Table 3-7 Controller Pre-Trip Test Codes (Sheet 1 Of 4) - Carrier 69NT40-511-310 Operation & Service Manual

Hide thumbs Also See for 69NT40-511-310:
Table of Contents

Advertisement

Code
No.
"Auto" or "Auto1" menu includes the: P, P1, P2, P3, P4, P5, P6 and rSLts. "Auto2" menu in-
cludes P, P1, P2, P3, P4, P5, P6, P7, P8, P9, P10 and rSLts."Auto3 menu includes P, P1, P2,
P3, P4, P5, P6, P7, P8 and rSLts
P
Pre-Trip Initiated
P1-0
Heaters Turned On
P1-1
Heaters Turned Off
P2-0
Condenser Fan On
P2-1
Condenser Fan Off
Low Speed Evapo-
P3
rator Fans
Low Speed Evapo-
P3-0
rator Fan Motors On
Low Speed Evapo-
P3-1
rator Fan Motors Off
High Speed Evapo-
P4-0
rator Fan Motors On
High Speed Evapo-
P4-1
rator Fan Motors Off
Supply/Return Probe
P5-0
Downloaded from
ManualsNet.com

Table 3-7 Controller Pre-Trip Test Codes (Sheet 1 of 4)

TITLE
All lights and display segments will be energized for five seconds at the start of
the pre-trip. Since the unit cannot recognize lights and display failures, there are
no test codes or results associated with this phase of pre-trip.
Setup: Heater must start in the OFF condition, and then be turned on. A current
draw test is done after 15 seconds.
Pass/Fail Criteria: Passes if current draw change is within the range specified.
Setup: Heater must start in the ON condition, and then be turned off. A current
draw test is done after 10 seconds.
Pass/Fail Criteria: Passes if current draw change is within the range specified.
Requirements: Water pressure switch (WP) input must be closed.
Setup: Condenser fan is turned ON, a current draw test is done after 15 sec-
onds.
Pass/Fail Criteria: Passes if current draw change is within the range specified.
Setup: Condenser fan is turned OFF, a current draw test is done after 10 sec-
onds.
Pass/Fail Criteria: Passes if current draw change is within the range specified.
Requirements: The unit must be equipped with a low speed evaporator fan, as
determined by the Evaporator Fan speed select configuration variable.
If the unit is configured for single evaporator fan operation, Pre-Trip tests
P3-0, P3-1, P4-0 and P4-1 will fail immediately if Controller alarm codes
AL11 or AL12 are active at the start of testing.
Setup: The high speed evaporator fans will be turned on for 10 seconds, then off
for two seconds, then the low speed evaporator fans are turned on. A current
draw test is done after 60 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range speci-
fied. Fails if AL11 or AL12 activates during test.
Setup: The low speed Evaporator Fan is turned off, a current draw test is done
after 10 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range speci-
fied. Fails if AL11 or AL12 activates during test.
Setup: The high speed Evaporator Fan is turned on, a current draw test is done
after 60 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range speci-
fied. Fails if AL11 or AL12 activates during test.
Setup: The high speed Evaporator Fan is turned off, a current draw test is done
after 10 seconds.
Pass/Fail Criteria: Passes if change in current draw is within the range speci-
fied. Fails if AL11 or AL12 activates during test.
Setup: The High Speed Evaporator Fan is turned on and run for eight minutes,
with all other outputs de-energized.
Pass/Fail Criteria: A temperature comparison is made between the return and
supply probes.
Test
If this test fails, "P5-0" and "FAIL" will be displayed. If both Probe tests (this
test and the PRIMARY/ SECONDARY) pass, the display will read "P5"
"PASS."
search engine
DESCRIPTION
NOTE
NOTE
NOTE
3-21
T-296